Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
171
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
r1204
Status word: flying start
V/f
-
-
-
-
-
U16
4
Bit parameter for checking and monitoring states during search.
Bit
Signal name
1 signal
0 signal
00
Current applied
Yes
No
01
Current could not be applied
Yes
No
02
Voltage reduced
Yes
No
03
Slope-filter started
Yes
No
04
Current less threshold
Yes
No
05
Current-minimum
Yes
No
07
Speed could not be found
Yes
No
P1210
Automatic restart
0 - 7
1
U, T
-
-
U16
2
Configures automatic restart function.
0
Disabled
1
Trip reset after power on, P1211 disabled
2
Restart after mains blackout, P1211 disabled
3
Restart after mains brownout or fault, P1211 enabled
4
Restart after mains brownout, P1211 enabled
5
Restart after mains blackout and fault, P1211 disabled
6
Restart after mains brown- /blackout or fault, P1211 enabled
7
Restart after mains brown- /blackout or fault, trip when P1211 expires
Dependency: Automatic restart requires constant ON command via a digital input wire link.
Caution:
P1210 > 2 can cause the motor to restart automatically without toggling the ON command!
Notice:
A "mains brownout" is a very short mains break, where the DC link has not fully collapsed before the
power is reapplied.
A "mains blackout" is a long mains break, where the DC link has fully collapsed before the power is re-
applied.
"Delay Time" is the time between attempts of quitting fault. The "Delay Time" of first attempt is 1 second,
then it will be doubled every next attempt.
The "Number of Restart Attempts" can be set in P1211. This is the number of restarts the inverter will try to
quit fault.
When faults are quit and after 4 seconds of no fault condition, "Number of Restart Attempts" will be reset
to P1211 and "Delay Time" will be reset to 1 second.
P1210 = 0:
Automatic restart is disabled.
P1210 = 1:
The inverter will acknowledge (reset) faults i.e. it will reset a fault when the power is re-applied. This
means the inverter must be fully powered down, a brownout is not sufficed. The inverter will not run until
the ON command has been toggled.
P1210 = 2:
The inverter will acknowledge the fault F3 at power on after blackout and restarts the inverter. It is
necessary that the ON command is wired via a digital input (DI).
P1210 = 3:
For these settings it is fundamental that the inverter only restarts if it has been in a RUN state at the time
of the faults (F3, etc.). The inverter will acknowledge the fault and restarts the inverter after a brownout. It
is necessary that the ON command is wired via a digital input (DI).