Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
154
Operating Instructions, 07/2012, A5E03728167
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
Note:
See P0844
P0848[0...2] BI: 1. OFF3
-
1
T
-
CDS
U32 /
Bin
3
Defines first source of OFF3 when P0719 = 0 (BICO).
Dependency: If one of the digital inputs is selected for OFF3, the inverter will not run unless the digital input is active.
Note:
OFF3 means quick ramp-down to 0.
OFF3 is low-active, i.e.
0 = Quick ramp-down.
1 = Operating condition.
P0849[0...2] BI: 2. OFF3
-
1
T
-
CDS
U32 /
Bin
3
Defines second source of OFF3.
Dependency: In contrast to P0848 (first source of OFF3), this parameter is always active, independent of P0719
(selection of command and frequency setpoint). See P0848.
Note:
See P0848
P0852[0...2] BI: Pulse enable
-
1
T
-
CDS
U32 /
Bin
3
Defines source of pulse enable / disable signal.
Dependency: Active only when P0719 = 0 (Auto selection of command / setpoint source).
P0881[0...2] BI: Quick stop source 1
-
1
T
-
CDS
U32 /
Bin
3
Allows quick stop source 1 command to be selected using BICO. The signal is expected to be active low
(default setting P0886 = 2).
P0882[0...2] BI: Quick stop source 2
-
1
T
-
CDS
U32 /
Bin
3
Allows quick stop source 2 command to be selected using BICO. The signal is expected to be active low
(default setting P0886 = 2).
P0883[0...2] BI: Quick stop override
-
0
T
-
CDS
U32 /
Bin
3
Allows quick stop override command source to be selected using BICO. The signal is expected to be
active high.
r0885.0...4
CO / BO: Quick stop
status
-
-
-
-
-
U16
3
Bit field describing status of quick stop.
Bit
Signal name
1 signal
0 signal
00
Quick stop is active
Yes
No
01
Quick stop selected
Yes
No
02
Override selected
Yes
No
04
Quick stop enabled
Yes
No
P0886[0...2] Quick stop input type
0 - 4
2
T
-
CDS
U16
3
Control Word for selecting the quick stop input type.
0
Quick stop not selected
1
Quick stop input active high
2
Quick stop input active low
3
Quick stop input positive edge triggered
4
Quick stop input negative edge triggered