The standard version of the drive is equipped with a PROFIBUS interface (slave). The "Anybus-X-
Gateway" supplied by HMS Industrial Networks is used to link the drive to the third-party bus
system. The X gateway is connected to the CU320 Control Unit using a PROFIBUS cable. The
option is supplied with a null modem cable for configuring the X gateway. The gateway is
preconfigured to 20 bytes of I/O data. The data size is changed via the configuration interface
from a PG/PC (standard PC tool "Windows Hyper Terminal").
Use the "NetTool" supplied by HMS Industrial Networks to configure PROFIBUS. The NetTool is not
included in the scope of supply.
3.5.44
Plug connection between the starting converter and excitation equipment
(option G57)
Three plug connections are provided in the cutout in the side panel. This is used to connect the
power unit of the starting converter with the open-loop control cabinet of the excitation
equipment. The sockets are permanently installed in the open-loop control cabinet side panel.
The corresponding connectors in the converter can be freely connected to the terminals with the
adequate lengths provided.
The connectors are defined for the following signal and supply voltages:
Table 3-3
Connector assignment for voltages less than 60 V
Signal name
Pin assignment = MBJ01DE001.CX-X24
24 V DC supply voltage
P24V
1
2
3
4
M24V
Enable signal from the starting converter power
unit
P24V
5
Signal
6
Protective trip from the starting converter power
unit
P24V
7
Signal
8
Protection of the damping element OK (optional) P24V
9
Signal
10
Reserve
Reserve
11
12
Reserve
13
14
Reserve
15
Table 3-4
Connector assignment for battery and voltages greater than 60 V (1AC)
Signal name
Pin assignment = MBJ01DE001.CX-X22
230 V AC 50 Hz supply voltage (this voltage can
differ depending on the particular country)
L
1
N
2
Description
3.5 Options
3rd Party LCI Control Upgrade
52
Operating Instructions, 02/2022, A5E31872818