The EC declaration of conformity for the product described here, which complies with the
European Directive 2006/95/EC and corresponding standards EN 61800-5-1 and EN 60204-1,
refers only to the low-voltage section in the power unit and the control cabinet.
B.2
Environmental conditions
Climatic environmental conditions
Table B-2
Climatic environmental conditions
Storage with suitable pack‐
aging
Transport with suitable
packaging
Operation (industrial)
Ambient temperature
-25° C to +70° C
-25° C to +70° C
5° C to +40° C
Relative humidity
5% to 95%
(Only low condensation is per‐
mitted. The device must be
completely dry before com‐
missioning.)
5 % to 95 %
(Only slight condensation is
permissible. The device must
be completely dry before com‐
missioning.)
5% to 85%
(Condensation is not permit‐
ted)
Other climatic conditions ac‐
cording to class
1K22 according to DIN EN
60721‑3‑1 (IEC 60721‑3‑1)
Icing not permissible
2K11 according to DIN EN
60721‑3‑2 (IEC 60721‑3‑2)
3K22 according to DIN EN
60721‑3‑3/A2:1997
(IEC 60721‑3‑3/Ed2.2:2008)
Pollution degree
2 without conductive pollu‐
tion according to DIN EN
50178 / VDE 0160
(IEC 62103)
2 without conductive pollu‐
tion according to DIN EN
50178 / VDE 0160
(IEC 62103)
2 without conductive pollu‐
tion according to DIN EN
50178 / VDE 0160
(IEC 62103)
Mechanical ambient conditions
Table B-3
Mechanical ambient conditions
Storage with suitable pack‐
aging
Transport with suitable
packaging
Operation
Class
1M11 according to
DIN EN 60721‑3‑1
(IEC 60721‑3‑1)
2M4 according to
DIN EN 60721‑3‑2
(IEC 60721‑3‑2)
3M11 according to
DIN EN 60721‑3‑3/A2:1997
(IEC 60721‑3‑3/Ed2.2:2008)
Technical specifications and drawings
B.2 Environmental conditions
3rd Party LCI Control Upgrade
144
Operating Instructions, 02/2022, A5E31872818