Technical specifications
6.2 Specific technical data
Power Module PM330
76
Hardware Installation Manual, 10/2016, A5E32844552B AD
Article no.
6SL3310-
1PE38-4AA0
1PE38-8AA0
1PE41-0AA0
Recommended cable cross-section for 480 V
- DC link infeed (2/3 converter power)
- Braking Module
4)
3 x 120 mm
2
35 mm²
3 x 150 mm
2
35 mm²
3 x 185 mm
2
35 mm²
Tightening torque for line, motor, DC link, and
ground cable
50 Nm / 443 lbf in
50 Nm / 443 lbf in
50 Nm / 443 lbf in
Dimensions: Width x height x depth (mm)
801 x 1621 x 393
801 x 1621 x 393
801 x 1621 x 393
Weight
235 kg
250 kg
250 kg
1)
The line supply must be capable of supplying the minimum short-circuit current so that the fuses trigger and consequen-
tial damage is avoided.
Note: If the minimum short-circuit current is not reached, the tripping time for the fuses increases, which may result in
consequential damage.
2)
When semiconductor fuses are used, they must be mounted in the same higher construction as the converter.
3)
The motor cables must be evenly distributed on both connection chambers.
4)
For connection of the Braking Module with rated power of 50 kW, P
20
power of 200 kW.