Connecting up, switching on
4.2 Line, motor and DC link connection
Power Module PM330
38
Hardware Installation Manual, 10/2016, A5E32844552B AD
4.2.6
DC link connection
Connecting an external Braking Module
PM330 Power Modules permit an external Braking Module to be connected via the DCP and
DCN DC link connecting terminals.
Characteristic data of the connecting terminals (@ U
line rated
380 V – 480 V / 500 V – 600 V /
690 V):
●
Supply voltage: up to 780 V / 970 V / 1160 V DC
●
Current carrying capacity:
–
At a 40 °C ambient temperature:
- 65 A / 52 A / 44 A continuous
- 260 A / 210 A / 173 A for a 22
% mark
-to-space ratio (20 s on, 70 s off)
–
At a 50 °C ambient temperature:
- 49 A / 39 A / 33 A continuous
- 195 A / 158 A / 130 A for a 22
% mark
-to-space ratio (20 s on, 70 s off)
A Braking Module is not available for the PM330 Power Modules for line voltages 3 AC 500 -
690 V.
Supplementary rectifier for higher pulse line harmonics
When using DC link connecting terminals DCP and DCN as infeed for an external
supplementary rectifier (current carrying capability, see the appropriate table in the Technical
data), the rectifier must have as a minimum a fully-controlled 6-pulse diode three-phase
bridge or a 6-pulse thyristor three-phase bridge and a 2
% line reactor.
The system (infeed transformer, reactor, busbars, fuses, ...) must be designed so that the
current distribution of the individual subrectifiers corresponds to the theoretically expected
value.
The short-circuit and overload protection must be adapted.
Note
It is only permissible to switch on the supplementary rectifier if the DC link has been
precharged by the Power Module.
Signal X9.8:"DC Link Charged" can be used for this purpose.
Summary of Contents for SINAMICS G120P PM330
Page 1: ......
Page 2: ......
Page 18: ...Introduction Power Module PM330 18 Hardware Installation Manual 10 2016 A5E32844552B AD ...
Page 97: ......
Page 98: ......