Technical specifications
6.2 Specific technical data
Power Module PM330
80
Hardware Installation Manual, 10/2016, A5E32844552B AD
Article No.
6SL3310-
1PG35-2AA0
Recommended cable cross-section for 500 V
- DC link infeed (2/3 converter power)
2 x 150 mm
2
Recommended cable cross-section for 690 V
- DC link infeed (2/3 converter power)
2 x 150 mm
2
Tightening torque for line, motor, DC link, and
ground cable
50 Nm / 443 lbf in
Dimensions: Width x height x depth (mm)
548 x 1695 x 393
Weight
162 kg
Minimum control cabinet size for installation of the
Power Module (width x height x depth)
800 mm x 2000 mm x 600 mm
1)
The line supply must be capable of supplying the minimum short-circuit current so that the fuses trigger and consequen-
tial damage is avoided.
Note: If the minimum short-circuit current is not reached, the rupture time for the fuses increases, which may result in
consequential damage.
2)
When semiconductor fuses are used, they must be mounted in the same higher construction as the converter.