Technical specifications
6.1 General technical data
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
69
Permissible inverter overload
The inverters have different load capabilities, "High Overload" and "Low Overload",
depending on the expected.
Figure 6-2
Load cycles, Low Overload" and "High Overload"
Note
Please note the base load (100
% power or current) for Low Overload is higher than the
base load for High Overload.
The load characteristics shown in the diagram are only examples. We recommend the use of
the "SIZER" engineering software to select the appropriate Power Modules based on the
load situation. See Configuring support (Page 88).
Definitions
•
LO base-load input current
100
% of the permissible input c
urrent with a
load cycle according to Low Overload.
•
LO base-load output current
100
% of the permissible output current with a
load cycle according to Low Overload.
•
LO base-load power
Power with LO base-load output current
•
HO base-load input current
100
% of the permissible input current with a
load cycle according to High Overload.
•
HO base-load output current
100
% of the permissible output current with a
load cycle according to High Overload.
•
HO base-load power
Power with HO base-load output current
•
Rated current I
N
Continuous current at the type rating, overload
not possible