Note
Fixing elements used
The following fixing elements are used:
•
M8 screw
•
Washer according to DIN EN ISO 7093-1 and locking element
Tightening torques:
•
electrical connections 50 Nm ±15 % (M12 bolts)
•
mechanical screw connections: 25 Nm ±15 % (M8 bolts)
Note
Adhesive label with danger and warning notes in English and French
The adhesive label with danger and warning notes in English and French subsequently
shown is included with the converter.
•
Attach the adhesive label in the appropriate language to the inside of the converter
cabinet, where it is clearly visible at all times.