Introduction
Power Module PM330
Hardware Installation Manual, 10/2016, A5E32844552B AD
17
Note
Principle of the precharging circuit
SINAMICS PM330 Power Modules include a half-controlled thyristor bridge as rectifier
circuit. As a result of the precharging principle with phase control, precharging is only started
when all of the enable signals are available and by setting the ON/OFF command
(p0840 = 1).
The DC link is then fully charged after approximately 400 ms.
The Power Modules can be used with the following Control Units, including all
communication versions with firmware version from 4.6 HF7 and higher.
•
CU230P-2 PN
6SL3243-0BB30-1FAx
•
CU230P-2 DP
6SL3243-0BB30-1PAx
•
CU230P-2 HVAC 6SL3243-0BB30-1HAx
Operation with Control Units other than those listed above is not permitted.