![Siemens SIMATIC S7-300 FM 350-1 Manual Download Page 59](http://html.mh-extra.com/html/siemens/simatic-s7-300-fm-350-1/simatic-s7-300-fm-350-1_manual_1265384059.webp)
Programming the FM 350-1
5.7 Programming FM 350-1 without FCs
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
59
Offset to the start
address
Parameters
Meaning
Byte 14
STS_COMP2
STS_COMP1
STS_CMP2
STS_CMP1
STS_STP
STS_STA
STS_LATCH
STS_SET
Bit 7: Latched state of comparator 2
Bit 6: Latched state of comparator 1
Bit 5: Status at output DO1
Bit 4: Status at output DO0
Bit 3: Status at digital input DI-Stop
Bit 2: Status at digital input DI-Start
Bit 1: New latch value for isochronous mode
Bit 0: Status at digital input DI-Set
Byte 15
–
STS_C_DOPARA
STS_RES_ZERO
STS_RES_SYNC
STS_T_CMP_V2
STS_T_CMP_V1
STS_L_PREPAR
STS_L_DIRECT
Bit 7: Reserve = 0
Bit 6: Change function of DO0/DO1, hysteresis or pulse duration
Bit 5: Status bit of zero transition, overflow, underflow or comparator
Resetting
Bit 4: Reset synchronization status bit
Bit 3: Load comparison value 2
Bit 2: Load comparison value 1
Bit 1: Load counter in preparation
Bit 0: Direct and preparatory loading of counter
Summary of Contents for SIMATIC S7-300 FM 350-1
Page 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Page 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Page 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Page 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Page 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...