Operating Modes, parameters and commands
7.3 Count modes
FM 350-1 Counter module
102
Manual, 05/2011, A5E03648639-01
Behavior at the Count Limits
If the counter
●
has reached one of the count limits when counting without a main count direction,
●
has reached the high count limit when counting with main count direction up, or
●
has reached the low count limit when counting with main count direction down
and another pulse then comes, the counter is set to the load value, from which it resumes
counting. An appropriate status bit is set in the DB.
Table 7- 13 Behavior at the Count Limits (Periodic Counting)
Count limit reached
Status bit in DB
High count limit
STS_OFLW is set
Low count limit
STS_UFLW is set
Terminating the Count with the Gate Stop Function
You can also terminate the count at any time with the gate stop function. Set the GATE_STP
input parameter of FC CNT_CTL1 for this.