Wiring the FM 350-1
3.3 Module status after power on
FM 350-1 Counter module
34
Manual, 05/2011, A5E03648639-01
3.3
Module status after power on
Default setting
Module status after power on and before any parameters were transferred:
●
No gate - i.e., the gate is open
●
Counter inputs with default setting for 5 V differential signals, track B not inverted; single
evaluation (refer to the section Signal Evaluation (Page 166))
●
0 to +32 bit counting range
●
Counter status zero
●
Set counter with signal at input DI Set (and zero mark) locked
●
Input delay for digital inputs DI Start, DI Stop and DI Set typically 1 µs
(max. frequency: 200 kHz, minimum pulse width: 2.5 µs)
●
Input delay at 24 V counter inputs: typically 1 µs
(max. frequency: 200 kHz, minimum pulse width: 2.5 µs)
●
Outputs DO0 and DO1 disabled
●
Pulse duration = 0
●
No hardware interrupts set
●
"Continuous count" mode is set
●
Status messages are updated