![Siemens SIMATIC S7-300 FM 350-1 Manual Download Page 147](http://html.mh-extra.com/html/siemens/simatic-s7-300-fm-350-1/simatic-s7-300-fm-350-1_manual_1265384147.webp)
Operating Modes, parameters and commands
7.4 Measuring modes
FM 350-1 Counter module
Manual, 05/2011, A5E03648639-01
147
Limit Monitoring
The following value ranges are permitted for limit value monitoring:
Table 7- 39 Value Range for Limit Monitoring at a Resolution of 1 µs
Low limit T
u
High limit T
o
0 to 119 999 999 μs
T
u
+1 to 120 000 000 μs
Table 7- 40 Value Range for Limit Monitoring at a Resolution of 1/16 µs
Low limit T
u
High limit T
o
0 to 1 919 999 999 μs
T
u
+1 to 1 920 000 000 μs
Possible Measuring Ranges with Error Indication
Table 7- 41 Period Measurement: Measuring Ranges and Errors at a Resolution of 1 µs
Resolution 1 µs
Period T
min
± Absolute error
Period T
min
± Absolute error
1 μs* (10 ± 0)
1 μs* (100 000 ± 10)
1 μs* (100 ± 0)
1 μs* (1 000 000 ± 100)
1 μs* (1 000 ± 0)
1 μs* (10 000 000 ± 1 002)
1 μs* (10 000 ± 1)
1 μs* (100 000 000 ± 10 020)
Table 7- 42 Period Measurement: Measuring Ranges and Errors at a Resolution of 1/16 µs
Resolution 1/16 µs
Period T
min
± Absolute error
Period T
min
± Absolute error
1/16 μs* (160 ± 1)
1/16 μs* (1 600 000 ± 160)
1/16 μs* (1 600 ± 1)
1/16 μs* (16 000 000 ± 1 600)
1/16 μs* (16 000 ± 3)
1/16 μs* (160 000 000 ± 16 000)
1/16 μs* (160 000 ± 20)
1/16 μs* (1 600 000 000 ± 160 000)
Function of the DI Start and DI Stop Digital Inputs
You can choose between the following functions for the digital inputs:
●
Level-controlled hardware gate
●
Edge-controlled hardware gate
Summary of Contents for SIMATIC S7-300 FM 350-1
Page 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Page 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Page 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Page 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Page 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...