Operating Modes, parameters and commands
7.4 Measuring modes
FM 350-1 Counter module
136
Manual, 05/2011, A5E03648639-01
Measurement sequence
FM 350-1 measures continuously. You define a specific update time in the parameter
settings.
The module returns the value "-1" until the first update time has expired. The first update
time starts when the gate has opened.
When the gate has opened, continuous measurement starts at the first pulse of the pulse
sequence to measure. The first measured value can not be calculated until the second pulse
was received.
On each expiration of the update time, a measured value is output at the checkback
interface (frequency, period or rpm.) The end of a measurement is reported at the
STS_COMP1 status bit. This bit is reset by the RES_ZERO and STS_RES_ZERO bits
according to the acknowledgement principle.
If the rotary direction is reversed within an update time, the measured value remains
indefinite for this measuring period. You can respond to any disturbance in the process by
evaluating the STS_DIR checkback bits (evaluation of the direction.)
Summary of Contents for SIMATIC S7-300 FM 350-1
Page 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Page 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Page 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Page 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Page 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...