![Siemens SIMATIC S7-300 FM 350-1 Manual Download Page 56](http://html.mh-extra.com/html/siemens/simatic-s7-300-fm-350-1/simatic-s7-300-fm-350-1_manual_1265384056.webp)
Programming the FM 350-1
5.7 Programming FM 350-1 without FCs
FM 350-1 Counter module
56
Manual, 05/2011, A5E03648639-01
Offset to the start
address
Parameters
Meaning
Byte 14
–
–
–
–
SET_DO1
SET_DO0
CTRL_DO1
CTRL_DO0
Bit 7: Reserve = 0
Bit 6: Reserve = 0
Bit 5: Reserve = 0
Bit 4: Reserve = 0
Bit 3: Control bit DO1
Bit 2: Control bit DO0
Bit 1: Enable DO1
Bit 0: Enable DO0
Byte 15
–
C_DOPARA
1)
RES_ZERO
RES_SYNC
T_CMP_V2
2)
T_CMP_V1
2)
L_PREPAR
2)
L_DIRECT
2)
Bit 7: Reserve = 0
Bit 6: Change function of DO0/DO1, hysteresis or pulse duration
Bit 5: Status bits of zero transition, overflow, underflow and comparator
Resetting
Bit 4: Reset synchronization status bit
Bit 3: Load comparison value 2
Bit 2: Load comparison value 1
Bit 1: Load counter in preparation
Bit 0: Direct and preparatory loading of counter
1)
Do not set this bit at the same time as bits 0, 1, 2 or 3 of byte 15.
2)
Do not set this bit at the same time as bit 6 of byte 15.
Summary of Contents for SIMATIC S7-300 FM 350-1
Page 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Page 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Page 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Page 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...