Operating Modes, parameters and commands
7.3 Count modes
FM 350-1 Counter module
106
Manual, 05/2011, A5E03648639-01
SW gate status
The status of the SW gate is indicated at the STS_SW_G bit in the DB of FC CNT_CTL1.
Cancel and interrupt function of the gate
In your gate function parameters, you can define whether the gate should cancel or interrupt
the count.
When the canceling gate function is active, the count stop when the gate closes, and is
restarted at the load value when the gate is retriggered (time
①
in the figure below):
&RXQWHUOHYHO
+LJKFRXQWOLPLW
/RDGYDOXH
/RZFRXQWOLPLW
*DWHVWDUW
*DWHVWDUW
*DWHVWRS
7LPH
Figure 7-13 Continuous down count, canceling gate function
When the interrupting gate function is active, the count stops when the gate closes, and
resumes at the last actual count value when the gate is retriggered (time
①
in the figure
below):
ແ
&RXQWHUOHYHO
8SSHUFRXQWOLPLW
/RDGYDOXH
/RZHUFRXQWOLPLW
*DWHVWDUW
*DWHVWDUW
*DWHVWRS
7LPH
Figure 7-14 Continuous up count, interrupting gate function