![Siemens SIMATIC S7-300 FM 350-1 Manual Download Page 110](http://html.mh-extra.com/html/siemens/simatic-s7-300-fm-350-1/simatic-s7-300-fm-350-1_manual_1265384110.webp)
Operating Modes, parameters and commands
7.3 Count modes
FM 350-1 Counter module
110
Manual, 05/2011, A5E03648639-01
Setting and Resetting the Outputs
If you set the behavior of an output to "Inactive", you can set and reset enabled outputs
using the appropriate bits in the DB.
Table 7- 18 Setting and Resetting the Outputs
Output
... Is set by
... Is reset by
DO0
SET_DO0 = 1
SET_DO0 = 0
DO1
SET_DO1 = 1
SET_DO1 = 0
Behavior of the Digital Outputs
For both digital outputs you can program one of 7 possible responses to reaching the
comparison value. The various options are shown in the table below.
Table 7- 19 Behavior of the Digital Outputs Depending on the Parameterization
Digital Output
Parameter
Assignment
Behavior of the Digital Outputs
8QGHUIORZ
&RPSDULVRQYDOXH
2YHUIORZ
Inactive
The output remains deactivated and is not affected by the comparison value,
zero crossing, overflow, or underflow events. The output DOx may be used
purely as a digital output. When enabled, it can be set and reset with the
SET_DOx bit.
8QGHUIORZ
&RPSDULVRQYDOXH
2YHUIORZ
Active from
comparison value to
overflow *
The output is set to 1 if the counter is in the range between the comparison
value and overflow.
Setting the counter to a value between the comparison value and overflow
sets the output to 1.
8QGHUIORZ
&RPSDULVRQYDOXH
2YHUIORZ
Active from
comparison value to
underflow *
The output is set to 1 if the counter is in the range between the comparison
value and underflow.
Setting the counter to a value between the comparison value and underflow
sets the output to 1.
Active on reaching
the comparison value
for pulse duration
(up)*
W
8QGHUIORZ
&RPSDULVRQYDOXH
2YHUIORZ
Summary of Contents for SIMATIC S7-300 FM 350-1
Page 8: ...Table of contents FM 350 1 Counter module 8 Manual 05 2011 A5E03648639 01 ...
Page 186: ...Technical data 11 2 Technical data FM 350 1 Counter module 186 Manual 05 2011 A5E03648639 01 ...
Page 188: ...Replacement parts FM 350 1 Counter module 188 Manual 05 2011 A5E03648639 01 ...
Page 190: ...References FM 350 1 Counter module 190 Manual 05 2011 A5E03648639 01 ...
Page 194: ...Glossary FM 350 1 Counter module 194 Manual 05 2011 A5E03648639 01 ...