S5-95F
Module Spectrum
*
without connection of a programmer, operator panel, text display or SINEC L1
For digital outputs (continued):
Total current
- for failsafe outputs
3 A
- for single-channel outputs
2 A
Driving of digital input
possible
Parallel switching of outputs
- for failsafe outputs
possible, if outputs
decoupled by a
diode
- for single-channel outputs
0.5 A each
Cable length, unshielded
max.
200 m (660 ft.)
Current consumption from 24 V
- for failsafe outputs
50 mA
(all outputs "0")
- for single-channel outputs
20 mA
(all outputs "0")
for interrupt inputs
Floating
yes
Input voltages and currents
as for digital inputs
(see Specific Onboard I/O Specifications)
Delay time
- from "0" to "1"
typ.
1 ms
- from "1" to "0"
typ.
1 ms
Pulse duration
*
2 ms
Cable length (shielded)
100 m (330 ft.)
Counter inputs
Floating
yes
Input voltages and currents
as for digital inputs
(see Specific Onboard I/O Specifications)
Delay time
- from "0" to "1"
typ.
1 ms
- from "1" to "0"
typ.
1 ms
Counter frequency
*
counter A: 350 Hz
counter B: 350 Hz
Pulse duration
1.4 ms
Cable length (shielded)
100 m (330 ft.)
EWA 4NEB 812 6210-02
A-3