● Dismantling machines with flameproof enclosures
● Connection work carried out in the terminal box
The operations must be identified by an additional repair plate carrying the following
information:
● Date
● Company carrying out repair
● Type of repair
● Reference number of the repair technician regarding repair work
Testing after repair shall be carried out in accordance with EU directives.
DANGER
Gap dimensions
Changing ignition gap geometries (gap dimensions) as part of repair work according to the
minimum specifications of IEC / EN 60079–1 is not permissible.
This can result in death, serious injury or material damage.
Obtain the gap dimensions of the electrical machine from the manufacturer for the repair or
restoration of ignition gap geometries.
WARNING
Rotating or live parts
Live electrical parts are dangerous. Contact with them can cause death, serious injury or
material damage.
Before carrying out any maintenance work on the external fan, disconnect it from the mains,
particularly before opening the terminal box. Make sure that the device cannot be switched
back on.
Maintenance
9.1 Inspection and maintenance
LOHER CHEMSTAR 1PS5
94
Operating Instructions 03/2014
Summary of Contents for SIMATIC S5 1P 243
Page 2: ...11 03 2014 02 49 V4 00 ...
Page 12: ...Introduction LOHER CHEMSTAR 1PS5 12 Operating Instructions 03 2014 ...
Page 20: ...Safety notes 2 11 Ventilation LOHER CHEMSTAR 1PS5 20 Operating Instructions 03 2014 ...
Page 66: ...Electrical connection 6 2 Connecting LOHER CHEMSTAR 1PS5 66 Operating Instructions 03 2014 ...
Page 124: ...Disposal 11 4 Disposal of components LOHER CHEMSTAR 1PS5 124 Operating Instructions 03 2014 ...
Page 136: ...Quality documents C 4 Data LOHER CHEMSTAR 1PS5 136 Operating Instructions 03 2014 ...
Page 140: ...Index LOHER CHEMSTAR 1PS5 140 Operating Instructions 03 2014 ...
Page 141: ...AC EC Declaration of Conformity U161 AB EC Declaration of Conformity U163 AA R No 20000h U165 ...