Note
Undrilled entry plate
If the entry plate is undrilled, you should match the number and size of the cable glands to
the operating conditions. Not applicable for terminal boxes of the Ex d type of protection.
1. Unscrew the cable entry plate.
2. Drill the required number of holes or threads in the required size into the cable entry plate.
The thickness of the plate is selected in such a way as to give a sufficient number of turns
when the holes are tapped.
Please note that you are responsible for ensuring that the entry plate still has sufficient
strength after the holes have been drilled and tapped.
3. Mount the cable entry plate and the cables with the cable glands onto the terminal box.
After the cables have been inserted into the terminal box, tighten the cable glands and parts
for strain relief to the torque specified by the manufacturer.
4. Seal the screwed sockets on the cable glands in accordance with the degree of protection.
Use only sealing plugs, cable entries and conductor entries, that are certified and marked for
use in the respective hazardous area (the zone).
6.2.9
Minimum air clearances
After proper installation, verify that the minimum air clearances between non-insulated parts
are maintained. Be aware of any protruding wire ends.
Table 6-4
Minimum air clearance dependent on rms value of the alternating voltage U
rms
Rms value of the alternating voltage V
rms
Minimum air clearance
≤ 500 V
8 mm
≤ 630 V
10 mm
≤ 800 V
12 mm
≤ 1000 V
14 mm
Values apply at an installation altitude of up to 2000 m.
When determining the required minimum air clearance, the voltage value in the table may be increased
by a factor of 1.1, so that the rated input voltage range is taken into account during general use.
Electrical connection
6.2 Connecting
LOHER CHEMSTAR 1PS5
60
Operating Instructions 03/2014
Summary of Contents for SIMATIC S5 1P 243
Page 2: ...11 03 2014 02 49 V4 00 ...
Page 12: ...Introduction LOHER CHEMSTAR 1PS5 12 Operating Instructions 03 2014 ...
Page 20: ...Safety notes 2 11 Ventilation LOHER CHEMSTAR 1PS5 20 Operating Instructions 03 2014 ...
Page 66: ...Electrical connection 6 2 Connecting LOHER CHEMSTAR 1PS5 66 Operating Instructions 03 2014 ...
Page 124: ...Disposal 11 4 Disposal of components LOHER CHEMSTAR 1PS5 124 Operating Instructions 03 2014 ...
Page 136: ...Quality documents C 4 Data LOHER CHEMSTAR 1PS5 136 Operating Instructions 03 2014 ...
Page 140: ...Index LOHER CHEMSTAR 1PS5 140 Operating Instructions 03 2014 ...
Page 141: ...AC EC Declaration of Conformity U161 AB EC Declaration of Conformity U163 AA R No 20000h U165 ...