3(
3(
3(
/
/
/
/
/
3(
/
/
/
Concentric copper or aluminum shield
Steel armor
Measures to further reduce bearing currents
To specifically reduce and prevent damage caused by bearing currents, you must consider
the system as a whole, which comprises the motor, converter, and driven machine. The
following precautions help to reduce bearing currents:
● In the overall system, set up a properly meshed grounding system with low impedance for
high-frequency currents.
● Use the common-mode filter (damping cores) at the converter output. The Siemens sales
representative is responsible for selection and dimensioning.
● Limit the rise in voltage by using output filters. This dampens the harmonic content in the
output voltage.
Note
Converter documentation
The operating instructions for the converter are not part of this documentation. Refer also
to the configuration information for the converter.
4.11.2
Insulated bearings when operating the converter
Depending on the machine's size and design, an insulated bearing and an insulated
tachometer can be fitted at the non-drive end.
Comply with the plates on the machine relating to bearing insulation and possible bridges.
①
Driving machine
④
Insulated bearings
②
Motor
⑤
Insulated tachometer fitting
③
Coupling
Figure 4-1
Schematic representation of a single drive
Preparations for use
4.11 Converter operation
LOHER CHEMSTAR 1PS5
Operating Instructions 03/2014
39
Summary of Contents for SIMATIC S5 1P 243
Page 2: ...11 03 2014 02 49 V4 00 ...
Page 12: ...Introduction LOHER CHEMSTAR 1PS5 12 Operating Instructions 03 2014 ...
Page 20: ...Safety notes 2 11 Ventilation LOHER CHEMSTAR 1PS5 20 Operating Instructions 03 2014 ...
Page 66: ...Electrical connection 6 2 Connecting LOHER CHEMSTAR 1PS5 66 Operating Instructions 03 2014 ...
Page 124: ...Disposal 11 4 Disposal of components LOHER CHEMSTAR 1PS5 124 Operating Instructions 03 2014 ...
Page 136: ...Quality documents C 4 Data LOHER CHEMSTAR 1PS5 136 Operating Instructions 03 2014 ...
Page 140: ...Index LOHER CHEMSTAR 1PS5 140 Operating Instructions 03 2014 ...
Page 141: ...AC EC Declaration of Conformity U161 AB EC Declaration of Conformity U163 AA R No 20000h U165 ...