plate of the machine. Information about the parameters is available in the operating instructions
for the converter.
WARNING
Exceeding limit values
It is not permissible that the maximum speed and torque values stamped on the
supplementary plate for converter operation are exceeded.
This can result in death, serious injury or material damage.
4.11.1
Reducing bearing currents during operation on the converter
Taking the following actions will reduce the bearing currents:
● Grounding:
– In addition to grounding the machines via the solid protective ground conductor,
supplement the high frequency grounding using braided flat copper straps or high
frequency stranded conductors.
– Ensure that the contacts cover a large area. Solid copper cables are not suitable for
high frequency grounding because of the skin effect.
● Use equipotential bonding conductors:
– Between motor and driven machine
– Between motor and converter
– Between terminal box and RF grounding point at the motor enclosure
● Use a separate RF equipotential bonding conductor:
– Between motor enclosure and protective ground rail of the converter
– Between motor enclosure and driven machine
● Selecting and connecting the cable: As far as possible, use symmetrically arranged,
shielded connection cables. The cable shielding, made up of as many strands as possible,
must have good electrical conductivity. Braided shields made of copper or aluminum are
very suitable.
– The shield must be connected at both ends to the motor and the converter; unshielded
cable ends must be kept as short as possible.
– To ensure good discharging of high-frequency currents, provide contacting over a large
surface area: with 360° contacting at the converter, at the motor for instance with EMC
screw fastenings at the cable entries.
Preparations for use
4.11 Converter operation
LOHER CHEMSTAR 1PS5
38
Operating Instructions 03/2014
Summary of Contents for SIMATIC S5 1P 243
Page 2: ...11 03 2014 02 49 V4 00 ...
Page 12: ...Introduction LOHER CHEMSTAR 1PS5 12 Operating Instructions 03 2014 ...
Page 20: ...Safety notes 2 11 Ventilation LOHER CHEMSTAR 1PS5 20 Operating Instructions 03 2014 ...
Page 66: ...Electrical connection 6 2 Connecting LOHER CHEMSTAR 1PS5 66 Operating Instructions 03 2014 ...
Page 124: ...Disposal 11 4 Disposal of components LOHER CHEMSTAR 1PS5 124 Operating Instructions 03 2014 ...
Page 136: ...Quality documents C 4 Data LOHER CHEMSTAR 1PS5 136 Operating Instructions 03 2014 ...
Page 140: ...Index LOHER CHEMSTAR 1PS5 140 Operating Instructions 03 2014 ...
Page 141: ...AC EC Declaration of Conformity U161 AB EC Declaration of Conformity U163 AA R No 20000h U165 ...