Program blocks
5.7 Blocks for analog value functions
RTU303xC
Operating Instructions, 06/2019, C79000-G8976-C382-06
291
Parameters
Parameters
Tag type / range of
values
Description
Input parameters
En
Enable parameter, see section Often used parameters
(Page 252).
Input 1 .. Input 4
Analog input / bit
memory
Event counter / usage
meter
The values of the configured inputs are processed by the
three types of calculation.
Inputs with the setting "Unused" are not evaluated.
Output parameters
Minimum
Analog memory bit
•
Configured as a
floating-point
number:
±3.402823 e-38 ..
±3.402823 e+38
•
Configured as a
counter:
0 .. 4294967295
Tag in which the obtained minimum value is output.
Maximum
Analog memory bit
•
Configured as a
floating-point
number:
±3.402823 e-38 ..
±3.402823 e+38
•
Configured as a
counter:
0 .. 4294967295
Tag in which the obtained maximum value is output.
Mean value
Analog memory bit
•
Configured as a
floating-point
number:
±3.402823 e-38 ..
±3.402823 e+38
•
Configured as a
counter:
0 .. 4294967295
Tag in which the calculated mean value is output.
Error
Digital output / bit
memory
Error display:
•
0: Block processing completed without errors
•
1: Block processing aborted with an error
For the meaning, see Often used parameters
(Page 252).