Configuration (WBM)
4.20 Extension board
RTU303xC
208
Operating Instructions, 06/2019, C79000-G8976-C382-06
●
Data type - Endianness
Use the drop-down list to determine how the RTU interprets the data of counters and
analog values read by the sensor.
The RTU always stores the two bytes of a word in the Big Endian format according to the
Modbus specification.
–
Example:
The two bytes of a word are numbered as follows: | 1 | 0 |
The higher byte 1 is stored first (Big Endian).
The following options are available:
–
Signed 16-bit value
–
Unsigned 16-bit value
–
Signed 32-bit value HW – LW
First High Word, then Low Word (Big Endian)
–
Signed 32-bit value LW – HW
First Low Word, then High Word (Little Endian)
–
Unsigned 32-bit value HW – LW
First High Word, then Low Word (Big Endian)
–
Unsigned 32-bit value LW – HW
First Low Word, then High Word (Little Endian)
–
Floating-point number (32-bit) HW – LW
First High Word, then Low Word (Big Endian)
–
Floating-point number (32-bit) LW – HW
First Low Word, then High Word (Little Endian)
●
Current sensor value
Display of the value of the input signal.
●
Current process value
Not displayed for variable type "Digital input".
Display of the converted process value, which is calculated from the sensor value after
the specification of the measuring range (see below).
●
Read
Click on the button to display the current value of the input.
Parameters for device type "HART"
●
Active
●
Name