Overview
1.9 Organizational measures
TP1000F Mobile RO
24
Operating Instructions, 08/2017, A5E39831415-AA
1.9
Organizational measures
Measures
If you are using a fail-safe Mobile Panel in a fail-safe system, you must consider the
following organizational measures:
●
Install stationary emergency stop or emergency off buttons in the plant that are effective
independent of the Mobile Panel.
●
Perform a risk analysis of the plant.
●
If the overall plant is not to be monitored from a single location, configure plant areas.
●
Select the same operating mode for all connection boxes in a contiguous plant area.
●
Create a safety program.
●
Run an acceptance test on the fail-safe automation system.
F-systems
The table below shows the F-systems that can be configured or installed for a given
connection box. Requirement is that you are using a fail-safe Mobile Panel.
Connection box
Hardwired F-system, no emergency
stop/stop bypass
Hardwired F-system with emergency
stop/stop bypass
compact
Yes
No
standard
Yes
No
advanced
No
Yes
Safety-related
operating mode
Stop button evaluated by safety relay
Stop button evaluated by safety relay
E-stop button evaluated by safety relay E-stop button evaluated by safety relay
1.10
Mobile Panel and connection box compatibility
The Mobile Panels 2nd Generation are not compatible with the connection box DP Basic and
connection box DP Plus.
Compatibility of Mobile Panels 2nd Generation – connection box PN Basic and PN Plus
The TP1000F Mobile RO is compatible with the following connection boxes:
●
Connection box PN Basic, article number 6AV6671-5AE01-0AX0
●
Connection box PN Plus, article number 6AV6671-5AE11-0AX0
Restrictions:
●
Only one hardwired F-system with a stop function and enabling function is permitted.