Technical specifications
9.5 Climatic ambient conditions
TP1000F Mobile RO
160
Operating Instructions, 08/2017, A5E39831415-AA
9.5
Climatic ambient conditions
9.5.1
Transport and storage conditions
The following information applies to an HMI device and connection box transported and
stored in their original packaging.
The HMI device meets the requirements of IEC 60721-3-2, Class 2K2 with the following
amendments and limitations:
Type of condition
Permitted range
Temperature
-20 ... +60 °C
Atmospheric pressure
1080 ... 660 hPa, corresponds to an elevation of 1000 m to 3500 m
Relative humidity
10 ... 90%, without condensation
Pollutant concentration
SO2: < 0.5 ppm; Relative humidity < 60%, no condensation
H
2
S: < 0.1 ppm; Relative humidity < 60%, no condensation
Note
•
Ensure that no condensation (dewing) develops on or inside the HMI device after
transporting it at low temperatures or after it has been exposed to extreme temperature
fluctuations.
•
The HMI device must have acquired room temperature before it is put into operation. Do
not expose the HMI device to direct radiation from a heater in order to warm it up. In case
of condensation, wait until the HMI device has dried completely or approximately 4 hours
before switching it on.
9.5.2
Operating Conditions
The HMI device is designed for mobile operation in a location protected from the weather.
The HMI device meets the requirements of IEC 60721-3-3, Class 3K3 with the following
amendments and limitations:
The following information applies to the HMI device and to the connection box.
Type of condition
Permitted range
Temperature, HMI device
0 ... 45 °C
Temperature, connection boxes 0 ... 55 °C
Atmospheric pressure
1080 ... 795 hPa, corresponds to an elevation of 1000 m to 2000 m
Relative humidity
10 ... 90 %, no condensation
Pollutant concentration
SO
2
: < 0.5 ppm; Relative humidity < 60%, no condensation