Parameterizing the Mobile Panel
5.13 Functions for service and commissioning
TP1000F Mobile RO
122
Operating Instructions, 08/2017, A5E39831415-AA
7.
To delete the file selected, press "Delete".
The Delete confirmation dialog is displayed. The file is deleted when you select "OK".
8.
To restore the data from the selected file, select "Restore".
The following dialog appears:
9.
Selecting "Yes" restores the data.
The "Transfer" dialog appears. A progress bar shows the status of the restore process.
When the restore operation is complete, the "Restore operation successfully completed."
message is displayed. The HMI device then restarts and remains in transfer mode.
10.
Remove the storage medium, if necessary.
The data from the storage medium is now restored on the HMI device.
Note
After restoring, a recalibration of the touch screen may be required, see also section
"Calibrating the touch screen (Page 85)".