Technical specifications
9.7 Technical specifications
TP1000F Mobile RO
Operating Instructions, 08/2017, A5E39831415-AA
169
A detailed description of the internal SCALANCE switches of both connection boxes is
available in the following documents:
●
Operating instructions "SCALANCE X-200"
https://support.industry.siemens.com/cs/ww/en/view/102051962
●
Configuration manual "SCALANCE X-200"
https://support.industry.siemens.com/cs/ww/de/view/109476763
Insulation testing, protection class and degree of protection
Insulation testing
The insulation strength is demonstrated in the type test with the following test voltages in
accordance with IEC 61131-2:
Circuits with rated voltage of U
i
Test voltage
< 50 V
500 V AC to other circuits / to ground
Protection class
Protection class III according to IEC 61131-2
Protection against foreign objects and water
The device meets the requirements of IEC 60529.
Degree of protection
Validity
IP65 all-round
•
For connection box compact:
The connection box has been installed as described in this
document.
•
For connection boxes standard and advanced:
All unused screw connections are capped.
Type 4X/Type 12 (indoor use only) Applies if indicated on the nameplate