Technical specifications
9.7 Technical specifications
TP1000F Mobile RO
170
Operating Instructions, 08/2017, A5E39831415-AA
9.7.4
Power consumption specifications
The connection box and Mobile Panel must be taken into consideration when calculating the
power consumption. The tables below show typical values for the power consumption.
Note
The actual power consumption may vary depending on the configuration and the load at the
interfaces of the Mobile Panel deviating from the specified values. The following factors
affect the power consumption, for example:
•
The display brightness set on the Mobile Panel
•
The load on the USB interface of the Mobile Panel
•
The length of the connecting cable
Connection box
Power consumption, typical
Connection box compact
0.5 W
Connection box standard
2.4 W
Connection box advanced
2.8 W
Mobile Panel
Power consumption, typical
TP1000F Mobile RO
10.8 W
9.7.5
Reaction times and safety characteristics for fail-safe operation
Note
Proof-test intervals
Proof-test interval of the device (Lifetime): 20 years. The device must be replaced after this,
at the latest.
Proof-test interval for safety-related operator controls dependent on the Safety Integrity Level
SIL:
•
SIL2: Function test 1 × per year
•
SIL3: Function test 1 × per month