Commissioning the device
4.3 Parameter assignment for Comfort Panel
Comfort Panels
Operating Instructions, 07/2017, A5E36770603-AB
97
Procedure
1.
Open the "Transfer Settings" dialog using the "Transfer" icon.
①
Transfer group
②
Digital signatures group
③
Transfer channel group
④
Button for parameter assignment of the transfer channel properties
2.
Change to the "General" tab.
3.
In the "Transfer" group, select whether you want to enable or disable "Transfer" mode.
Select one of the following options:
–
Off – Transfer is not possible
–
Manual – Manual transfer
If you want to initiate a transfer, close the active project and press the "Transfer"
button in the Start Center.
–
Automatic – Automatic transfer
A transfer can be remotely triggered from a configuration PC or a programming
device. The running project is closed immediately in this case and the transfer is
started.
WARNING
Unintended reactions during automatic transfer
When an automatic transfer starts and the running project is closed immediately, this
could cause unintentional reactions to be triggered in the plant. This can result in
personal injury or material damage.
Take the following measures to prevent undesired reactions in the plant:
•
Select the "Off" or "Manual" setting for "Transfer" after the commissioning phase.
•
Assign a password in the Control Panel to restrict access to the transfer settings
by unauthorized persons.