Commissioning the device
4.3 Parameter assignment for Comfort Panel
Comfort Panels
132
Operating Instructions, 07/2017, A5E36770603-AB
Procedure
1.
Open the "WinCC Internet Settings" dialog using the "WinCC Internet Settings" icon.
2.
Change to the "Web Server" tab.
3.
In the "Tag acces" group, define the type of access to the tags of the server HMI device.
–
"Read/write": Read and write access
–
"Read only": Read access
4.
In the "Tag auhenticate" group, define the authentication required for access to the tags
of the server HMI device:
–
"No authentication": No authentication required.
–
"Authentication required": A password is required to access tags.
Configure a connection with password protection for access using SIMATIC HMI
HTTP Protocol. In this case, you must select the "Authentication required" option; the
associated password on the HMI device must match the password of the configured
connection.
5.
Select the options for starting and closing the Web Server.
–
If the Web Server is to be started immediately after power-up of the HMI device, select
the "Start automatically after booting" option. If this option is disabled, the Web Server
must be started manually using the "Start Web-Server" button or a corresponding
element in the project.
–
Select the "Close with Runtime" option if the Web Server is to be closed together with
the project. If this option is disabled, the Web Server continues running after the
project is closed.
6.
Press the "User Administration" button.
7.
If you are prompted to enter the administrator password, enter the password. The
"UserDatabase-Edit" dialog box opens.
8.
To create a new user, click "Add" in the "User Manager" tab. Enter a user name and
specify a password. The user enters the associated password when accessing the Web
Server.
9.
Save the settings using "Apply".
10.
Change to the "Authorizations" tab.