5 Interfaces
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules)
29 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
There are organisational and projected numbers for programming.
Organisational number:
displayed on the operating panel and on the printer.
Projected number:
required for internal processing and displayed on the printer.
The object number must have 3 digits and must be between 100 and 999. It is not possible to
assign a number twice (in SM88 and SIGMASYS). The projected number and the organisa-
tional number must be the same.
The organisational zone number must have 5 digits and is made up of the 3-digit object num-
ber and the 2-digit projected zone number.
The projected zone number must have 2 digits and must be between 01 and 99.
89 zones can be provided for each object.
Detector groups must always be entered with a projected number in the activation list for a
control module output (object/zone/detector group).
Example
Object
ZONE
Detector group
Detector
Object org.
101
Object proj.
101
Zone org.
101
11
Zone proj.
101
11
Detector group org.
___ 1
Detector group proj.
0001
Control org.
___ 1
Control proj.
0001
Activation list MG 1
101
11
0001
Table 15: Programming in SIGMAPLAN
Object
ZONE
Detector group
Detector
Object org.
101
Zone org.
101
11
Activation via zone
101
11
at the
printer
Detector group org.
___ 1
Control org.
___ 1
Activation via
101
11
0001
at the
printer
Table 16: Operating panel display
Summary of Contents for SIGMASYS C
Page 4: ......
Page 30: ......
Page 38: ......
Page 44: ...6 Functions 36 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Page 48: ......
Page 62: ......
Page 84: ......
Page 110: ......
Page 128: ...16 Appendix 120 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Page 130: ......
Page 132: ......
Page 134: ......
Page 137: ......