4 Project planning for control and indicating panels
4.2.2
Control room requirements
The control and indicating panel is to be installed in a controlled environment.
Permitted ambient conditions:
Temperature range:
0 °C to +40 °C
Atmospheric humidity.
<75 %, short-term 95 % without condensation
Protect the control and indicating panel from harmful environmental influences, such as direct
sunlight, operation-related vibrations, dust, etc.
Always ensure adequate heat dissipation before installing the control and indicating panel in a
recess or other enclosed space or under a cover.
Ensure that the room is adequately lit (DIN 14675).
Installation near heating elements or washbasins is prohibited.
We recommend laying a conductive floor covering (conductive PVC covering, conductive
needle felt covering) to protect the operating personnel against the unpleasant effects of sta-
tic charging.
4.2.3
SIGMASYS control and indicating panel: installation dimensions
Figure 1: Dimensions for the SIGMASYS control and indicating panel
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules)
13 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)