12 Monitored lines
12.4
Line lengths in the loop/spur
Shielded installation cables, e. g. IY(ST)Y are to be used as lines for the loop.
The maximum wire diameter that can be clamped in the standard detector base is 0.8 mm.
The maximum line length depends on:
•
the number of detectors and the cable type
•
the maximum line resistance including the resistance of the connected elements (R
max. = 200
Ω
)
•
the maximum line capacity including all connected capacities (C max. = 200 nF).
Ohm/km, or . element
nF/km, or element
IY (St) Y 2x2x0,8
73,2 Ohm
100 nF
IY (St) Y 2x2x0,6
130 Ohm
100 nF
NYM 1,5 mm²
25 Ohm
250 nF
Loop element
0,8 Ohm
-
Table 29: Line parameter
Element capacity is very low with regard to the line capacity and therefore not relevant.
The combo detector SDF3500 counts as two address elements in the per-detector line length
calculation.
Figure 17 shows the relationships for a 0.8 diameter line. The spur line is a real subset of the
loop line, i.e. up to 64 address elements can be operated on a 2 km line both in the loop and
on the spur. A large number of address elements can only be operated in the loop, the maxi-
mum possible line length drops to approx. 11 m
⁄
element.
Figure 15: Address element number and line lengths for a 0.8 diameter line
Behaviour is similar in the case of a 0.6 diameter line. The maximum line length here is 1.540
m in the case of
zero
elements. The maximum possible line length per element drops by ap-
prox. 6
m
⁄
element
and measures 1.150 m in length with 64 address elements (spur/loop) and 750
in the case of a fully configured loop (128 address elements).
Multifunctional Danger Control and Indicating Panels SIGMASYS C and M (M-Modules)
83 / 128
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
Summary of Contents for SIGMASYS C
Page 4: ......
Page 30: ......
Page 38: ......
Page 44: ...6 Functions 36 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Page 48: ......
Page 62: ......
Page 84: ......
Page 110: ......
Page 128: ...16 Appendix 120 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Page 130: ......
Page 132: ......
Page 134: ......
Page 137: ......