3 Guidelines for project planning
8 / 128
BMT Project Planning Guidelines
Best.Nr. A24205-A337-B970 – Edition 12 (03/07)
The following must be observed when constructing fire alarm systems in compliance with the
guidelines EN45, VdS 2095 (Association of German Underwriters) and DIN VDE 0833,
Part 2:
Monitored alarm line as loop (ring cable)
Up to 128 detectors and devices (automatic detectors, non-automatic detectors [manual call
points], transponders, indicator panel control facilities) can be connected here and multiple
fire sections with a total surveillance area of up to 6000 m
2
can be monitored.
Monitored alarm line as a spur
Multiple detector zones with up to 32 automatic or 10 non-automatic fire detectors can be
connected in a fire section.
3.1
Limitations
Detector zone limitations are:
A surveillance area of up to 1600 m
2
A detector zone must not exceed a fire section.
In the event of a monitored line fault
A maximum of 32 automatic or 10 non-automatic detectors may fail on a loop or spur in a de-
tector zone.
Only control facilities associated with the relevant detector zone may fail.
3.2
Guidelines for failure of the display unit and signal processor
Failure of
Effects in the case of < 512 de-
tectors <12.000 m
2
Effects in the case of >512 de-
tectors >12.000 m
2
Display unit (operating panel)
By displaying a general indication.
Integrated in the operating panel in
SIGMASYS G.
Additional operating panel or zone
operating panel or indicator panel
or printer.
Signal processor (SOC or MPC)
Control and indicating panel may
fail.
No effect on the remaining signal
processing operations.
Network e.g. 4 control and indicat-
ing panels with <12.000 m
2
each =
<48.000 m
2
Redundancy not re-
quired. Redundancy required for
systems with a surveillance area
>48.000 m
2
.
No fault in the event of failure of a
routing path.
Information to superordinate con-
trol and indicating panel must be
guaranteed (fault signal from rele-
vant control and indicating panel
and alarm signal).
Table 1: Guidelines for failure of the display unit and signal processor
3.3
Overvoltage protection measures
SIGMASYS control and indicating panels come with fine protection.
If required, medium and coarse protection for the O/E areas must be integrated in the line
network (in accordance with the VdS 2095/VdS2833 guidelines and the standard collection
SIG 01-01, GMS 03-01 A24205-A334-A790).
Summary of Contents for SIGMASYS C
Page 4: ......
Page 30: ......
Page 38: ......
Page 44: ...6 Functions 36 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Page 48: ......
Page 62: ......
Page 84: ......
Page 110: ......
Page 128: ...16 Appendix 120 128 BMT Project Planning Guidelines Best Nr A24205 A337 B970 Edition 12 03 07 ...
Page 130: ......
Page 132: ......
Page 134: ......
Page 137: ......