Controller
6.8 Parameters
ATE500E
System Manual, 09/2017, A5E33917696-AD
79
6.8.2
Forces
The following forces and currents can be parameterized for the driving curve:
Continuous torque (power) OPEN
Continuous torque in the door position OPEN.
This parameter is effective when an open command is present and the door is in the OPEN
position.
The current generates a continuous torque against the end position of the door in the
opening direction.
See also Figure 6-9 Current – force – motor characteristic in the opening and closing
directions (Page 81).
Adjustment ranges
The parameter can be adjusted in accordance with the adjustment ranges of the parameters
(see Section Profiles and adjustment ranges (Page 148)). The value of the parameter must
be selected so that the door is held in the OPEN position.
Continuous torque (power) CLOSE
Continuous torque in the door position CLOSED.
This parameter is effective when a close command is present and the door is in the
CLOSED position.
The current generates a continuous torque against the end position of the door in the closing
direction.
See also Figure 6-9 Current – force – motor characteristic in the opening and closing
directions (Page 81).
Adjustment ranges
The parameter can be adjusted in accordance with the adjustment ranges of the parameters
(see Section Profiles and adjustment ranges (Page 148)). The value of the parameter must
be selected so that the door is held in the CLOSED position.
Cutter press-on torque
The cutter press-on torque presses the door against a door cutter.
If an obstruction is detected within a tolerance range of 1 cm around the CLOSED position,
then the cutter press-on torque is applied for approx. 2 seconds.
Adjustment ranges
The parameter can be adjusted in accordance with the adjustment ranges of the parameters
(see Section Profiles and adjustment ranges (Page 148)). The value of the parameter must
be selected so that the cutter force opposing the door is overcome, and the door is closed
completely.