Power supply
8.2 SIDOOR NT40
ATE500E
System Manual, 09/2017, A5E33917696-AD
113
8.2.3
Connection
Requirements
WARNING
Dangerous electrical voltage!
When electrical devices are operated, parts of these devices will necessarily carry
dangerous voltages. Failure to observe the operating instructions can therefore lead to
serious injuries or material damage.
Observe the operating instructions.
Observe the following connection specifications:
●
The regulations for the construction of high voltage installations must be observed when
carrying out the electrical installation.
●
The switch mode power supply may only be connected to the power supply by connected
supply lines.
●
The power supply (230 V AC ±15%) must be connected according to VDE 0100 and VDE
0160.
●
The supply voltage to the device must be equipped with a protective device (miniature
circuit breaker) (10 A / tripping characteristic B).
●
The protective conductor is connected via the supply line X1.
●
Output lines may only to be connected to the SIDOOR controller.
●
When the device is connected to the power supply, it must be ensured that this supply
meets the requirements of overvoltage category II (see EN 60950-1:2006). If necessary,
external overvoltage protection must be connected upstream in order to comply with the
requirements of overvoltage category II (see EN 60950-1:2006).
You will find the description of the complete electrical setting and commissioning of the
controller and its associated components in Section Connection and commissioning
(Page 137).