Address Min/Max Value Parameters
Default
Unit
Type
75
0 to 100
Number of pulses for operate
0
–
uInt16
76
0 to 100
Number of pulses for monitoring
0
–
uInt16
77
0, 2 to 999
Nos det.
0
–
ulnt16
78
0 to 600
T-det. ext
0
s
ulnt16
79
11
0
1
Correction factor disabled
Correction factor enabled
0
–
ulnt16
80
0, 700 to 3000
V
1
magnitude factor
(correction factor disabled)
0
1/1000 ulnt16
V
1
magnitude factor
(correction factor enabled)
1000
81
-500 to 500
V
1
angle offset
0
min
Int16
82
0, 700 to 3000
V
2
magnitude factor
(correction factor disabled)
0
1/1000 ulnt16
V
2
magnitude factor
(correction factor enabled)
1000
83
-500 to 500
V
2
angle offset
0
min
Int16
84
0, 700 to 3000
V
3
magnitude factor
(correction factor disabled)
0
1/1000 ulnt16
V
3
magnitude factor
(correction factor enabled)
1000
85
-500 to 500
V
3
angle offset
0
min
Int16
86
0, 800 to 1200
I
1
magnitude factor
(correction factor disabled)
0
1/1000 ulnt16
I
1
magnitude factor
(correction factor enabled)
1000
87
-500 to 500
I
1
angle offset
0
min
Int16
88
0, 800 to 1200
I
2
/I
N
magnitude factor
(correction factor disabled)
0
1/1000 ulnt16
I
2
/I
N
magnitude factor
(correction factor enabled)
1000
89
-500 to 500
I
2
/I
N
angle offset
0
min
Int16
90
0, 800 to 1200
I
3
magnitude factor
(correction factor disabled)
0
1/1000 ulnt16
I
3
magnitude factor
(correction factor enabled)
1000
91
-500 to 500
I
3
angle offset
0
min
Int16
For more information about register-type data – input registers, see
B.5 Register-Type Data – Input Registers
11
Default values in holding addresses 80 to 91 are dependent on whether the parameter Correction factor (holding register 79) is disa-
bled or enabled.
Modbus Registers
B.2 Implementation of the Modbus Protocol
SICAM, Feeder Condition Monitor, Manual
99
E50417-H8940-C580-A4, Edition 03.2019