Table B-6
Input Registers
Address Min/Max Value Parameters
Unit
Type
1000
0 to 65535
Phase current I
1
A
uInt16
1001
0 to 65535
Phase current I
2
A
uInt16
1002
0 to 65535
Phase current I
3
A
uInt16
1003
0 to 65535
Ground current I
N
for compensated/isolated
systems
1/100 A
uInt16
0 to 9999
Ground current I
N
for grounded systems
A
1004
0 to 65535
Voltage V
12
1/10 V for 230-V
sensor
uInt16
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1005
0 to 65535
Voltage V
23
1/10 V for 230-V
sensor
uInt16
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1006
0 to 65535
Voltage V
31
1/10 V for 230-V
sensor
uInt16
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1007
0 to 65535
Voltage V
1
1/10 V for 230-V
sensor
uInt16
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1008
0 to 65535
Voltage V
2
1/10 V for 230-V
sensor
uInt16
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1009
0 to 65535
Voltage V
3
1/10 V for 230-V
sensor
uInt16
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1010
0 to 65535
Displacement voltage V
NG
1/10 V for 230-V
sensor
uInt16
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1011
0 to 3599
Phase angle I
1
1/10°
uInt16
1012
0 to 3599
Phase angle I
2
1/10°
uInt16
Modbus Registers
B.2 Implementation of the Modbus Protocol
100
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019