Table B-12
Date and Time – Seconds
Bit
15
14
13
12
11
10
9
8
Milliseconds
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
Milliseconds
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
16-bit unsigned integer
Range
0 to 59999 ms
Default
0
(Address 6)
Table B-13
Date and Time – Hours/Minutes
Bit
15
14
13
12
11
10
9
8
Not used
Not used
Not used
Hours
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
Not used
Not used
Minutes
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Hours
Format
5-bit unsigned integer
Unit
h
Range
0 to 23
Minutes
Format
6-bit unsigned integer
Unit
Min
Range
0 to 59
(Address 7)
Table B-14
Date and Time – Date/Month
Bit
15
14
13
12
11
10
9
8
Not used
Month
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
Not used
Date
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Month
Format
4-bit unsigned integer
Unit
Month
Range
1 to 12
Date
Format
5-bit unsigned integer
Unit
Date
Range
1 to 31
(Address 8)
Modbus Registers
B.4 Register-Type Data – Holding Registers
SICAM, Feeder Condition Monitor, Manual
111