
▶
PULSETH OP.
▶
0 to 100
(Set to "0" to disable the
detection function)
▶
SAVE
▶
PULSETH MON. ▶
0 to 100
(Set to "0" to disable the
detection function)
▶
SAVE
▶ INTERMIT-
TENT
GROUND
FAULT
▶
NOS. DET.
▶
0 to 999
(Set to "0" to disable the
detection function)
▶
SAVE
▶
T-DET.EXT
▶
0 to 600
(Set to "0" to disable the
detection function)
▶
SAVE
Table A-4
Parameters Menu Structure - Fault Parameters
FAULT
PARAME-
TERS
▶
OVERVOLTAGE
ALERTS
▶
OVERVOLTAGE
WARNING
▶
0 % to 30 %
(Set to "0" to disable the overvoltage
warning)
▶
SAVE
▶
OVERVOLTAGE
ALARM
▶
0 % to 30 %
(Set to "0" to disable the overvoltage alarm)
▶
SAVE
▶
UNDER-
VOLTAGE
ALERTS
▶
UNDER-
VOLTAGE
WARNING
▶
0 % to 30 %
(Set to "0" to disable the undervoltage
warning)
▶
SAVE
▶
UNDER-
VOLTAGE
ALARM
▶
0 % to 30 %
(Set to "0" to disable the undervoltage alarm)
▶
SAVE
▶
OVERCURRENT
ALERTS
▶
OVERCURRENT
WARNING
▶
50 A to 2000 A
(Set to "0" to disable the detection function)
▶
SAVE
▶
OVERCURRENT
ALARM
▶
50 A to 2000 A
(Set to "0" to disable the detection function)
▶
SAVE
▶
OVERCURRENT
TWARNING
▶
1 min to 120 min
(Set to "0" to disable the overcurrent
warning)
▶
SAVE
▶
OVERCURRENT
TALARM
▶
1 min to 120 min
(Set to "0" to disable the overcurrent alarm)
▶
SAVE
▶
AUTO RESET
TIME
▶
0 min to 480 min
(Set to "0", auto reset is immediate on fault restoration)
▶
SAVE
Parameterization
A.2 Parameterizing the User Interface
SICAM, Feeder Condition Monitor, Manual
87
E50417-H8940-C580-A4, Edition 03.2019