
▶
TIME SETTING
tV
NG
>
▶
0.04 s to 60 s
▶
SAVE
▶
I
dir
▶
0.2 A to 30 A
(Set to "0" to disable the
cos
ϕ
/sin
ϕ
method)
▶
SAVE
▶
NEUTRAL-POINT
TREATMENT
▶
SOLID or ISOLATED or RESO-
NANT
▶
SAVE
▶ GROUP2
SETTING
▶
GROUND-FAULT
DETECTION I
N
>
▶
0.4 A to 2000 A
(Set to "0" to disable the
detection function)
▶
SAVE
▶
GROUND-FAULT
DETECTION tI
N
>
▶
0.04 s to 60 s
▶
SAVE
▶
THRESHOLD
SETTING V
NG
>
▶
0 % to 100 %
(Set to "0", the ground-fault
detection is based on I
N
>)
▶
SAVE
▶
TIME SETTING
tV
NG
>
▶
0.04 s to 60 s
▶
SAVE
▶
I
dir
▶
0.2 A to 30 A
(Set to "0" to disable the
cos
ϕ
/sin
ϕ
method)
▶
SAVE
▶
NEUTRAL-POINT
TREATMENT
▶
SOLID or ISOLATED or RESO-
NANT
▶
SAVE
▶ V<
▶
0 % to 100 %
(Set to "0" to disable the detection function)
▶
SAVE
▶ V>
▶
0 % to 170 %
(Set to "0" to disable the detection function)
▶
SAVE
▶ PULSE
DETEC-
TION
▶
3I0 DELTA
▶
0 % to 300 %
(Set to "0" to disable the
detection function)
▶
SAVE
PULSE
DETEC-
TION
▶
TPULSE ON
▶
0.50 s to 20 s
(Set to "0" to disable the
detection function)
▶
SAVE
▶
TPULSE OFF
▶
0.50 s to 20 s
(Set to "0" to disable the
detection function)
▶
SAVE
Parameterization
A.2 Parameterizing the User Interface
86
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019