[dw_fcm_block_diagram2322, 2, en_US]
Figure 2-2
SICAM FCM Block Diagram for MLFB 6MD2322-1AA00-1AA0
Applications
SICAM FCM is used:
•
As a directional and non-directional short circuit and ground-fault detector suitable for solid, isolated, and
compensated networks in medium-voltage and low-voltage distribution systems
•
As a simple power quality meter and energy measurements in various applications
Flush Mounting
SICAM FCM can be flush-mounted in the panel and operated inside an enclosed dry room. To mount
SICAM FCM in the panel, proceed as follows:
•
Cut a rectangle in the Ring-Main Unit (RMU) panel measuring 92.0 mm + 0.8 mm × 45.0 + 0.8 mm (W ×
H).
•
Carry out all the required internal wiring connections.
For more information about terminal diagrams, refer to
•
Flush SICAM FCM into the panel and lock it with the clamps.
•
For more information about installation, refer to
Device Ordering Information
Use the following ordering information to order SICAM FCM and other related accessories.
Introduction
2.1 Overview
SICAM, Feeder Condition Monitor, Manual
15
E50417-H8940-C580-A4, Edition 03.2019