Implementation of the Modbus Protocol
The device operates as a Modbus Remote Terminal Unit (RTU) slave.
Modbus Function Codes
Function Code
Function as per Modbus Specification
Description
01
Read coils
Bit access to BIT-AREA
02
Read discrete inputs
Bit access to BIT-AREA
03
Read holding registers
16-bit access to REGISTER-AREA
04
Read input registers
16-bit access to REGISTER-AREA
05
Write single coil
Bit access to BIT-AREA
06
Write single register
16-bit access to REGISTER-AREA
15
Write multiple coils
Bit access to BIT-AREA
16
Write multiple registers
16-bit access to REGISTER-AREA
If the device receives an unsupported function code, it returns the exception code response as 01.
Data-Package Format
Table B-1
Communication Settings
Baud rate (bps)
2400, 4800, 9600, 19200, 38400, 57600, 115200
Parity
O/E/N
Table B-2
Modbus Parameters
Modbus ID
1 to 247
0 - Broadcast
248 to 255 Special
Modbus type
RTU
In the SICAM FCM, the data-byte standard setting is as follows:
•
1 start bit
•
8 data bits (LSB first)
•
1 parity bit (odd/even/none)
•
1 stop bit
Modbus Data
The device supports the following data types:
•
Bit-type data (discrete inputs/coil)
•
Register-type data
The following abbreviations are used for the register names:
Input Registers
Inp-Reg
Holding Registers
Hold-Reg
For more information about bit-type data - coil, see
B.2
Modbus Registers
B.2 Implementation of the Modbus Protocol