Phase Current I
1
(Address 306, 316, …., 496) This register contains the fault current in I
1
.
Bit
15
14
13
12
11
10
9
8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
16-bit unsigned integer
Unit
A
Range
0 to 9999
Phase Current I
2
(Address 307, 317, …., 497) This register contains the fault current in I
2
.
Refer to
Phase Current I
3
(Address 308, 318, …., 498) This register contains the fault current in I
3
.
Refer to
Ground Current I
N
(Address 309, 319, …., 499) This register contains the fault ground current in I
N
.
Bit
15
14
13
12
11
10
9
8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
16-bit unsigned integer
Unit
1/10 A for solid and isolated/resonant connection
Range
0 to 9999 for solid connection
0 to 65535 for isolated/resonant connection
Reserved
(Address 310 to 500) These registers are reserved.