
Overvoltage Alarm Time (Hours and Minutes)
(Address 8) This register contains the alarm time in hours and minutes.
Refer to
Last Reset Time (Hours and Minutes), Page 144
.
Overvoltage Alarm Time (Month and Date)
(Address 9) This register contains the alarm time in month and date.
Refer to
Last Reset Time (Month and Date), Page 144
Overvoltage Alarm Time (Year)
(Address 10) This register contains the overvoltage alarm time in years.
Refer to
Last Reset Time (Year), Page 145
Overvoltage Warning Type
(Address 11) This register defines the phase in which the overvoltage warning is occurred.
Bit
15
14
13
12
11
10
9
8
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
Not used
Not used
Not used
Not used
Not used
V
3
V
2
V
1
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
16-bit unsigned integer
Unit
–
Range
–
Overvoltage Warning Time (Milliseconds)
(Address 12) This register contains the overvoltage warning time in milliseconds.
Refer to
Last Reset Time (Milliseconds), Page 144
Overvoltage Warning Time (Hours and Minutes)
(Address 13) This register contains the overvoltage warning time in hours and minutes.
Refer to
Last Reset Time (Hours and Minutes), Page 144
.
Overvoltage Warning Time (Month and Date)
(Address 14) This register contains the overvoltage warning time in month and date.
Refer to
Last Reset Time (Month and Date), Page 144
Overvoltage Warning Time (Year)
(Address 15) This register contains the overvoltage warning time in years.
Refer to
Last Reset Time (Year), Page 145
Undervoltage Alarm Type
(Address 16) This register defines the phase in which the undervoltage alarm is occurred.
Bit
15
14
13
12
11
10
9
8
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
Not used
Not used
Not used
Not used
Not used
V
3
V
2
V
1
Modbus Registers
B.6 Register-Type Data – Analog Input Registers
146
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019