[lo_sfcm_pulse_pattern_mech, 1, en_US]
Figure 4-15
Network in Pulse-Location Detection
C
S
Capacitance of the switched capacitor
L
Inductance of the Petersen coil
The
shows the ground-current pulse pattern in an overcompensated system for a low-impedance
ground fault and a high-impedance ground fault.
•
For low-impedance ground faults, the pulse pattern exists only in the faulty feeder.
•
For high-impedance ground faults, the pulse pattern is also present in the healthy feeders with lower
amplitude but in phase opposition to the faulty feeder.
Using different values of the parameters
Pulse-on duration (TPulse ON)
and
Pulse-off
duration (TPulse OFF)
, the differentiation between healthy and faulty feeders for high-impedance
ground faults can be ascertained.
Device Functions
4.1 Description
SICAM, Feeder Condition Monitor, Manual
47
E50417-H8940-C580-A4, Edition 03.2019