
▶
CROSSBLOCK
TIMER
▶
0 ms to 60 000 ms
▶
OK
▶
TIMER LOGIC
▶
TIMER LOGIC T1 ▶
0 to 60 s
(Enhanced fault validation and reset function
is disabled)
▶
SAVE
▶
TIMER LOGIC T2 ▶
0 to 25 s
(Enhanced fault validation and reset function
is disabled)
▶
SAVE
▶
TIMER LOGIC T2 ▶
0 to 240 s
(Enhanced fault validation and reset function
is disabled)
▶
SAVE
Table A-5
Parameters Menu Structure - Timer Logic and Process Parameters
PROCESS
PARAMETERS
▶
CORRECTION
FACTOR
▶
DISABLE (Default)
▶
ENABLE
▶
VOLTAGE
PARAMETERS
▶
LV TO MV CALCU-
LATION
▶
TRANSFORMER
TYPE
▶
DY-11
▶
TRANSFORMER
ANGLE
▶
0° to 359°
▶
SAVE
▶
PRIMARY
VOLTAGE
CORRECTION
▶
0 V to 900 V
▶
SAVE
▶
CAPACITIVE
VOLTAGE MEAS-
UREMENT
▶
AUTO CALIBRA-
TION VOLTAGE
▶
1000 V to 36000 V
▶
SAVE
▶
AUTO CALIBRA-
TION
▶
START AUTO CALI-
BRATION
▶
OK
▶
RATED SEC.
VOLTAGE
▶
AC 3.25/√3 or AC 100/√3 V or AC 230 V or
AC 400/√3
▶
SAVE
▶
RATED PRI.
VOLTAGE
▶
1.0 kV to 36.0 kV
▶
SAVE
▶
SENSOR VOLTAGE
PRIMARY
▶
1.0 kV to 36.0 kV
▶
SAVE
▶
VOLTAGE CORREC-
TION FACTOR
▶
V
1
MAGNITUDE
FACTOR
▶
V
1
ANGLE OFFSET
▶
V
2
MAGNITUDE
FACTOR
▶
V
2
ANGLE OFFSET
Parameterization
A.2 Parameterizing the User Interface
88
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019