Register-Type Data – Trailing Pointers
(Address 101 to 282) This register stores the minimum value and the maximum value of I
1
, I
2
, I
3
, I
N
, P, Q, and
the S values for the respective phases at regular intervals. The interval ranges are 15 minutes, 30 minutes, 45
minutes, 60 minutes, 24 hours, 1 month, and 1 year.
Table B-16
Trailing Pointers
Parame-
ters
15 Minutes 30 Minutes
45 Minutes 60 Minutes 24 Hours
1 Month
1 Year
Min
value
Max
value
Min
value
Max
value
Min
value
Max
value
Min
value
Max
value
Min
value
Max
value
Min
value
Max
value
Min
value
Max
value
I
1
101
114
127
140
153
166
179
192
205
218
231
244
257
270
I
2
102
115
128
141
154
167
180
193
206
219
232
245
258
271
I
3
103
116
129
142
155
168
181
194
207
220
233
246
259
272
I
N
104
117
130
143
156
169
182
195
208
221
234
247
260
273
P
1
105
118
131
144
157
170
183
196
209
222
235
248
261
274
P
2
106
119
132
145
158
171
184
197
210
223
236
249
262
275
P
3
107
120
133
146
159
172
185
198
211
224
237
250
263
276
Q
1
108
121
134
147
160
173
186
199
212
225
238
251
264
277
Q
2
109
122
135
148
161
174
187
200
213
226
239
252
265
278
Q
3
110
123
136
149
162
175
188
201
214
227
240
253
266
279
S
1
111
124
137
150
163
176
189
202
215
228
241
254
267
280
S
2
112
125
138
151
164
177
190
203
216
229
242
255
268
281
S
3
113
126
139
152
165
178
191
204
217
230
243
256
269
282
Phase Current I
1
) This register contains the minimum values and the maximum values of the phase
current I
1
measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Bit
15
14
13
12
11
10
9
8
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
Bit
7
6
5
4
3
2
1
0
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Format
16-bit unsigned integer
Unit
A
Range
0 to 9999
Phase Current I
2
) This register contains the minimum values and the maximum values of the phase
current I
2
measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
.
Phase Current I
3
) This register contains the minimum values and the maximum values of the phase
current I
3
measured every 15/30/45/60 minutes, 24 hours, 1 month, and 1 year respectively.
Refer to
.
B.8
Modbus Registers
B.8 Register-Type Data – Trailing Pointers
SICAM, Feeder Condition Monitor, Manual
153
E50417-H8940-C580-A4, Edition 03.2019